600 amp dc power system

Product Information

Guardian Access 23 is a 5RU/6RU high 23” rack-mounted, integrated 600 amp DC power system providing an output of -48VDC. These systems can accommodate up to five (5U) or ten (6U) Guardian family high efficiency hot-swap rectifiers.

A load current of 500A is available with battery charge current up to 145A software controlled, subject to an overall 600A. The rectifiers are internally fan cooled with speed control which is a function of load and temperature, keeping acoustic noise to a minimum.

The DC output circuits can provide up to 26 loads which utilize circuit breakers with capacities from 2A to 150A plus up to six 100A or 125A breakers that provide battery protection. A programmable 500A low voltage battery disconnect (LVBD) is standard while one or two partial load disconnects (PLD), rated at 125A or 200A and also programmable, can provide non-critical load shedding when operating on batteries.

THREE YEAR WARRANTY

Looking for the 19″ rack-mount version of this product? Click HERE.
Features and Options
  • >96% Efficiency Rectifiers
  • 600A / 29kW Total Capacity
  • Remote Monitoring & Control
  • Intelligent Battery Management
  • Field Replaceable Controller
  • Ethernet Comm. with SNMPv3
  • 3 LED Alarm/Status Indicators
  • Up to 10 Form-C Relay Alarms
  • Up to 26 Load Breakers
  • Up to 6 Battery Breakers
  • LCD Display/Touchpad
  • Easy Installation
SPECIFICATIONS
 
OUTPUT
System Voltage-48VDC nominal | -53.5 float (factory default setting, user adjustable)
Maximum Capacity @ 120VAC nominal Load - 318A
Battery - 318A discharge | 145A charge (s/w controlled)
Maximum Capacity @ 230/400VAC nominal Load - 500A
Battery - 500A discharge | 145A charge (s/w controlled)
No. Rectifier Slots 5 (5RU) or 10 (6RU)
 
DC DISTRIBUTION
Loads Circuits Up to 26 x 18mm (2A to 150A)
Battery Circuits1-6 x (100A or 125A)
 
INPUT
Voltage (nominal)1-phase 100-120/200-240VAC (L + N + PE)
3-phase 230/400VAC (L1 L2 L3 + N + PE)
Frequency47-63Hz
Maximum Input Current 200A @ 100-120VAC | 169A @ 200-240VAC | 56A per phase @ 400/230VAC
Rectifier Power Factor>0.98 (typical)
Surge ProtectionOptional
 
MONITORING & CONTROL (ACC Extended Controller)
Alarm Relays4 standard, option for 10
Local Interface 4 x 20 LCD, 4-key menu, USB / RS232, microSD card slot (4GB max,) for data logging
Remote InterfaceEthernet / Modem using PowCom™ software package
Ethernet port allows monitoring and control over a TCP/IP network.
Web browser support + SNMPv3
LED IndicationsGreen - System ON; Yellow - Message(s); Red LED - Alarm(s)
External Digital I/O 2 x Inputs, 2 x Outputs (TTL Level)
 
BATTERY MANAGEMENT
Symmetry Inputs6 or 12 (can be redefined as analog inputs up to 100VDC)
Low Voltage Battery Disconnect (LVBD) 1 x 500A Programmable
Partial Load Disconnect (PLD)1 or 2 x 125A or 200A Programmable (Optional)
Temperature Compensated ChargingProgrammable
 
COMPLIANCE
EMCEN 300 386 ; EN61000-6-3 (Emission) ; EN61000-6-2 (Immunity)
SafetyIEC60950-1:2005 2 Ed. +A1:2009
 
ENVIRONMENTAL
Operating Temperature-40ºC to +55ºC
Storage Temperature-40ºC to +85ºC
 
DIMENSIONS, ins. (mm)
M24 23.2 (589) W x 5RU or 6RU H x 15.0 (382) D
MS32 23.2 (589) W x 5RU or 6RU H x 16.9 (430) D
INTELLIGENT BATTERY MANAGEMENT
(PROVIDED VIA ACC EXTENDED CONTROLLER)
Battery Disconnection Provides voltage controlled disconnection of batteries.
Boost Charging Manual time controlled or automatic boost charging with adjustable time and voltage levels.
Battery Tests Automatic or manual testing of batteries up to six times per year with a 10 test memory. Variables include test duration and end voltage.
Battery discontinuance test to ensure battery connection.
Enhanced Battery Monitoring Monthly logging of essential battery parameters including temperature, temperature hours, current, charging voltage and symmetry voltage, Data logged for 5 years.
Site Logs System tools developed to assist site management. Daily peak load and statistic logs available.
Symmetry Measurement Optional tool that measures batteries for early detection of thermal runaway.
Temperature Compensation Charging

Allows continuous adjustment of output voltage according to battery temperature.
Features include adjustable compensation factor and separate thresholds for high temperature alarms.

Load Shedding (PLD) Optional feature that allows voltage or time controlled disconnection of non-essential load.