SABRE Series

Product Information

SABRE Series are 3kVA to 9kVA hot swap inverter systems that operate from a 48VDC (40.5-58V range) input and produce either 120VAC or 230VAC nominal output.

The low distortion 50 or 60Hz sine wave is produced using an advanced DSP controlled Architecture which achieve better than 89% efficiency and 10.5VA per cubic inch power density.

SABRE Series pre-configured 3kVA to 9kVA hot swap inverter systems include a Controller and Static Transfer Switch with optional Power Distribution and Maintenance By-Pass facilities.

These 3kVA to 9kVA hot swap inverter systems include remote Communications to a PC is provided USB, RS232 or RS485 serial connections.  SNMP alarm traps delivered over an Ethernet TPC/IP connection are also provided as standard.

TWO YEAR WARRANTY

Features and Options
  • Hot-Swap Replacement in Shelves
  • 19- or 23-Inch Rack Mounting
  • 120 or 230VAC Output
  • 50 or 60Hz Low Distortion Sine Wave
  • 40.5 to 58 VDC Input
  • 1500 VA Module Output
  • Scalable to 18kVA
  • 10.5 VA per Cubic Inch Density
  • Fully Isolated from Battery Input
  • 90% Typical Efficiency
  • DSP Management & Control
  • Smart Fan Speed Control
  • Powers Reactive Loads
  • Parallel Capable
  • N+1 Redundant Operation
  • LED Status Indicators
SPECIFICATIONS
 
INVERTER MODULES
INPUT
Voltage Range 40.5-58VDC
Undervoltage Warning Threshold 45VDC
Undervoltage Threshold 40VDC
Overvoltage Warning Threshold 58VDC
Overvoltage Threshold 60VDC
Input Current, 48VDC Input 28.4A
Input Protection Fused Reverse Polarity Protection
Inrush Current Less than 2x Rated Iin (IEC62040-3-1999)
Isolation Input to Output - Reinforced Pri-Sec, 4242VDC / 1 min.
Input to Ground - 707VDC (Varistor & filter caps removed)
Psophometric Noise Voltage <1mV ITU-T 0.41 (16.66-6000Hz)
Reflected Psophometrics Noise Current <1% YD/T 777-2006
Reflected Relative Band Wide Current <10% YD/T 777-2006 (0-2MHz)
Wide Band Noise <20mVrms (25Hz-20kHz)
Peak to Peak Noise <150mV up to 100MHz
 
OUTPUT
Rated Output Voltage

120VAC or 230VAC (see model table)

AC Waveform Pure Sine Wave
Power 1500VA @ 0.8PF or 1200W @ 1PF
Power Factor of Load -0.8 to +0.8
Voltage Setpoints Available (via controller) INV1548 [120VAC factory set]: 110,115 or 120VAC
INV1548H [ 230VAC factory]: 208, 220, 230, 240VAC
Voltage Variation <±2%
Nominal Frequency 50Hz or 60Hz (see model table)
Frequency Variation <±0.5%
Crest Factor 3:1 max.
THD of Voltage Waveform Linear Load: <3%
Non-Linear Load: <5%
Capacitive/Inductive Load +0.8 to +0.8 PF [without exceeding permissible distortion for resistive load]
Efficiency >89%
Overload Protection Electronic Current Limit at Overload & Short Circuit, 1.25 x Rated Current, Temperature Controlled, 1.50 x Rated Current for Periods <20 Seconds
Dynamic Response <±10%
Isolation, Output to Chassis Basic Isolation (Pri-Gnd) 2121 VDC/1 min.
Surge Protection EN61000-4-5, Telcordia GR-1089 Core, ANSI C62.41-IEEE, STD 587-1980
Load Sharing <5% of Rated Load
 
CONTROL & STATUS
LED Indicators Inverter Status: Green OK, Red FAIL
Overload: Off OK, Yellow for Overload
Reverse Polarity: Off OK, Red for Reversed
Status/Alarm Information (via controller) Inverter Fail, Overload, LVD Alarm, Fail Alarm, Thermal Derating, Power Output, Input Voltage, Output Voltage, Output Current, Output
Frequency, Low Input Voltage Shutoff, Inventory Data
Runtime Info. Through Maintenance Feature in Controller
 
STATIC TRANSFER SWITCH
INPUT
Voltage Range 110/115/120VAC Systems: 89-138VAC
208/220/230/240VAC Systems: 176-276VAC
Over / Undervoltage Threshold (adjustable from controller) 110VAC Systems: 117 to 127VAC / 89 to 105VAC
115VAC Systems: 122 to 132VAC / 93 to 110VAC
120VAC Systems: 127 to 138VAC / 100 to 114VAC
208VAC Systems: 220 to 240VAC / 176 to 198VAC
220VAC Systems: 233 to 252VAC / 176 to 209VAC
230VAC Systems: 244 to 264VAC / 185 to 218VAC
240VAC Systems: 254 to 276VAC / 193 to 228VAC
 
OUTPUT
AC Waveform Sine Wave
Output Voltage Same as utility or inverter modules
Permissible Frequency Variation to Synchronise Inverters ±2.5%
Transfer Time Typically 1/4 cycle
Rated Current 3kVA & 6kVA - 50A / 9kVA - 100A
Operation Modes (programmable) Inverter Priority or Utility Priority
Default Priority Inverters
 
CONTROL/STATUS
LED Indicators Fault (red): Off OK, On FAIL
Warning (yellow): Off OK, Flashing for warning condition
Power On (green): On OK, Flashing for bypass
Status/Alarm Information CAN communication failure, back-feed relay open, SCR short, uutput short, overload over temperature, mains unavailable, inverter unavailable
output abnormal, fan failure, MBS position error
 
GENERAL
ENVIRONMENTAL
Operating Temp. Range Without Derating: -5°C to 50°C
With Derating: -20°C to 70°C
Storage Temp. Range -40°C to +85°C
Humidity 0% to 95%, Non-Condensing
Cooling (Inverter & STS modules only) Variable Speed Internal Fans (Field Replaceable)
Operating Altitude 1500m without derating
 
REGULATORY
Safety (Individual modules) Inverter/PDU/MBS/chassis: UL60950-1, EN60950-1, IEC60950-1
STS module: UL1778
EMC (individual modules) EN300 386:2001 Class B
Acoustic Noise (individual modules) 55dB ETS300 753, Class 3.1
INVERTER MODULES
MODELS MAX OUTPUT POWER OUTPUT VOLTAGE FREQUENCY
INV1548 1500VA @ 0.8PF
12W @ 1.0PF*
120VAC 60Hz (50Hz)**
INV1548H 1500VA @ 0.8PF
12W @ 1.0PF*
230VAC 50Hz (60Hz)**
NOTE:
*If in doubt about load PF (Power Factor) assume it is 1.0PF.
** The frequency shown in brackets can be obtained by reprogramming the unit from the system controller.

FULLY INTEGRATED PRE-CONFIGURED/ASSEMBLED SYSTEM UNITS
MODELS MAX.
OUTPUT POWER
MAX NO.
MODULES
OUTPUT
VOLTAGE
DISTRIBUTION
SOCKET TYPE
MANUAL
BYPASS
RACK
HEIGHT
IX2U-1-TS50S-120
IX2U-1-TS50S-230
3kVA, 2.4kW 2 120VAC
230VAC
none N 2U
IX3U-1-TS50S-D1N-120 3kVA, 2.4kW 2 120VAC only 6 x NEMA N 3U
IX3U-1-TS50S-D1E-120
IX3U-1-TS50S-D1E-230
3kVA, 2.4kW 2 120VAC
230VAC
6 x IEC60-320 N 3U
IX4U-1-TS50S-D2N-120 3kVA, 2.4kW 2 120VAC only 8 x NEMA Y 4U
IX4U-1-TS50S-D2E-120
IX4U-1-TS50S-D2E-230
3kVA, 2.4kW 2 120VAC
230VAC
8 x IEC60-320 Y 4U
IX3U-2-TS50S-120
IX3U-2-TS50S-230
6kVA, 4.8kW 4 120VAC
230VAC
none N 3U
IX4U-2-TS50S-D1N-120 6kVA, 4.8kW 4 120VAC only 6 x NEMA N 4U
IX4U-2-TS50S-D1E-120
IX4U-2-TS50S-D1E-230
6kVA, 4.8kW 4 120VAC
230VAC
6 x IEC60-320 N 4U
IX5U-2-TS50S-D2N-120 6kVA, 4.8kW 4 120VAC only 8 x NEMA Y 5U
IX5U-2-TS50S-D2E-120
IX5U-2-TS50S-D2E-230
6kVA, 4.8kW 4 120VAC
230VAC
8 x IEC60-320 Y 5U
IX5U-3-TS100S-120
IX5U-3-TS100S-230
9kVA, 7.2kW 6 120VAC
230VAC
none N 5U
IX6U-3-TS100S-D1N-120 9kVA, 7.2kW 6 120VAC only 6 x NEMA N 6U
IX6U-3-TS100S-D1E-120
IX6U-3-TS100S-D1E-230
9kVA, 7.2kW 6 120VAC
230VAC
6 x IEC60-320 N 6U
IX7U-3-TS100S-D2-120
IX7U-3-TS100S-D2-230
9kVA, 7.2kW 6 120VAC
230VAC
none Y 7U
NOTES:
All models include Static Transfer Switch Module, Controller Module and Communications with SNMP Alarm Trapping.
Inverter modules must be ordered separately based on output voltage and total system capacity required. Module types may not be mixed in the same system.
120VAC inverters are pre-programmed to 60Hz, 230VAC inverters are pre-programmed to 50Hz. These settings can be changed from the front panel of the controller or remotely using the WINpower client application.

IMPORTANT NOTE – ALL SABRE IX SYSTEMS ARE SHIPPED AS “MID-MOUNT” ASSEMBLIES.
FLUSH-MOUNT IS AVAILABLE, THOUGH NOT RECOMMENDED.